Length of Wire using Area of X-Section(Single Phase Two Wire Mid-Point Earthed OS) Solution

STEP 0: Pre-Calculation Summary
Formula Used
Length of Overhead AC Wire = (Area of Overhead AC Wire*Maximum Voltage Overhead AC^2*Line Losses*cos(Phase Difference)^2)/(Resistivity*Power Transmitted^2)
L = (A*Vm^2*Ploss*cos(Φ)^2)/(ρ*P^2)
This formula uses 1 Functions, 7 Variables
Functions Used
cos - Cosine of an angle is the ratio of the side adjacent to the angle to the hypotenuse of the triangle., cos(Angle)
Variables Used
Length of Overhead AC Wire - (Measured in Meter) - Length of Overhead AC Wire is the total length of the wire from one end to other end.
Area of Overhead AC Wire - (Measured in Square Meter) - Area of Overhead AC Wire is defined as the cross-sectional area of the wire of an AC supply system.
Maximum Voltage Overhead AC - (Measured in Volt) - Maximum Voltage Overhead AC is defined as the peak amplitude of the AC voltage supplied to the line or wire.
Line Losses - (Measured in Watt) - Line Losses is defined as the total losses occurring in an Overhead AC line when in use.
Phase Difference - (Measured in Radian) - Phase Difference is defined as the difference between the phasor of apparent and real power (in degrees) or between voltage and current in an ac circuit.
Resistivity - (Measured in Ohm Meter) - Resistivity is the measure of how strongly a material opposes the flow of current through them.
Power Transmitted - (Measured in Watt) - Power Transmitted is defined as the product of current and voltage phasor in a overhead ac line at the receiving end.
STEP 1: Convert Input(s) to Base Unit
Area of Overhead AC Wire: 0.79 Square Meter --> 0.79 Square Meter No Conversion Required
Maximum Voltage Overhead AC: 62 Volt --> 62 Volt No Conversion Required
Line Losses: 8.23 Watt --> 8.23 Watt No Conversion Required
Phase Difference: 30 Degree --> 0.5235987755982 Radian (Check conversion here)
Resistivity: 1.7E-05 Ohm Meter --> 1.7E-05 Ohm Meter No Conversion Required
Power Transmitted: 890 Watt --> 890 Watt No Conversion Required
STEP 2: Evaluate Formula
Substituting Input Values in Formula
L = (A*Vm^2*Ploss*cos(Φ)^2)/(ρ*P^2) --> (0.79*62^2*8.23*cos(0.5235987755982)^2)/(1.7E-05*890^2)
Evaluating ... ...
L = 1392.01089434638
STEP 3: Convert Result to Output's Unit
1392.01089434638 Meter --> No Conversion Required
FINAL ANSWER
1392.01089434638 1392.011 Meter <-- Length of Overhead AC Wire
(Calculation completed in 00.004 seconds)

Credits

Created by Urvi Rathod
Vishwakarma Government Engineering College (VGEC), Ahmedabad
Urvi Rathod has created this Calculator and 1500+ more calculators!
Verified by Payal Priya
Birsa Institute of Technology (BIT), Sindri
Payal Priya has verified this Calculator and 1900+ more calculators!

12 Wire Parameters Calculators

Length of Wire using Area of X-Section(Single Phase Two Wire Mid-Point Earthed OS)
Go Length of Overhead AC Wire = (Area of Overhead AC Wire*Maximum Voltage Overhead AC^2*Line Losses*cos(Phase Difference)^2)/(Resistivity*Power Transmitted^2)
Line Losses using Area of X-Section(Single Phase Two Wire Mid-Point Earthed OS)
Go Line Losses = (Length of Overhead AC Wire*Resistivity*Power Transmitted^2)/(Area of Overhead AC Wire*Maximum Voltage Overhead AC^2*cos(Phase Difference)^2)
Area of X-Section using Line Losses (Single Phase Two Wire Mid-Point OS)
Go Area of Overhead AC Wire = (Resistivity*Length of Overhead AC Wire*Power Transmitted^2)/(Line Losses*(Maximum Voltage Overhead AC*cos(Phase Difference))^2)
Volume of Conductor Material using Line Losses (Single Phase Two Wire Mid-Point OS)
Go Volume of Conductor = (2*Resistivity*Power Transmitted^2*Length of Overhead AC Wire^2)/(Line Losses*Maximum Voltage Overhead AC*cos(Phase Difference)^2)
Area of X-Section(Single Phase Two Wire Mid-Point Earthed)
Go Area of Overhead AC Wire = (Power Transmitted^2*Resistivity*Length of Overhead AC Wire)/(((cos(Phase Difference))^2)*Line Losses*Voltage Overhead AC^2)
Constant using Load Current (Single Phase Two Wire Mid-Point OS)
Go Constant Overhead AC = (8*Current Overhead AC^2*cos(Phase Difference)^2*Resistivity*Length of Overhead AC Wire^2)/Line Losses
Constant using Line Losses (Single Phase Two Wire Mid-Point OS)
Go Constant Overhead AC = (4*Resistivity*Power Transmitted^2*Length of Overhead AC Wire^2)/(Line Losses*Maximum Voltage Overhead AC^2)
Constant (Single Phase Two Wire Mid-Point Earthed)
Go Constant Overhead AC = (4*Power Transmitted^2*Resistivity*Length of Overhead AC Wire)/(Line Losses*Voltage Overhead AC^2)
Length using Load Current (Single Phase Two-Wire Mid-Point OS)
Go Length of Overhead AC Wire = (Line Losses*Area of Overhead AC Wire)/(2*(Current Overhead AC)^2*Resistivity)
Volume of Conductor Material using Load Current (Single Phase Two Wire Mid-Point OS)
Go Volume of Conductor = (4*(Current Overhead AC^2)*Resistivity*(Length of Overhead AC Wire^2))/(Line Losses)
Area of X-Section using Load Current (Single Phase Two Wire Mid-Point OS)
Go Area of Overhead AC Wire = (2*Current Overhead AC^2*Resistivity*Length of Overhead AC Wire)/(Line Losses)
Line Losses using Load Current (Single Phase Two Wire Mid-Point OS)
Go Line Losses = 2*Current Overhead AC^2*Resistance Overhead AC

Length of Wire using Area of X-Section(Single Phase Two Wire Mid-Point Earthed OS) Formula

Length of Overhead AC Wire = (Area of Overhead AC Wire*Maximum Voltage Overhead AC^2*Line Losses*cos(Phase Difference)^2)/(Resistivity*Power Transmitted^2)
L = (A*Vm^2*Ploss*cos(Φ)^2)/(ρ*P^2)

What is the value of maximum voltage and volume of conductor material in this system?

The volume of conductor material required in this system is 1/2cos2θ times that of 2-wire d.c.system with the one conductor earthed. The maximum voltage between conductors is 2vm so that r.m.s. value of voltage between them is √2vm.

How to Calculate Length of Wire using Area of X-Section(Single Phase Two Wire Mid-Point Earthed OS)?

Length of Wire using Area of X-Section(Single Phase Two Wire Mid-Point Earthed OS) calculator uses Length of Overhead AC Wire = (Area of Overhead AC Wire*Maximum Voltage Overhead AC^2*Line Losses*cos(Phase Difference)^2)/(Resistivity*Power Transmitted^2) to calculate the Length of Overhead AC Wire, The Length of Wire using Area of X-section(single Phase two Wire Mid-point Earthed OS) formula is defined as the total length of the wire that used in the single-phase two-wire mid-point earthed system. Length of Overhead AC Wire is denoted by L symbol.

How to calculate Length of Wire using Area of X-Section(Single Phase Two Wire Mid-Point Earthed OS) using this online calculator? To use this online calculator for Length of Wire using Area of X-Section(Single Phase Two Wire Mid-Point Earthed OS), enter Area of Overhead AC Wire (A), Maximum Voltage Overhead AC (Vm), Line Losses (Ploss), Phase Difference (Φ), Resistivity (ρ) & Power Transmitted (P) and hit the calculate button. Here is how the Length of Wire using Area of X-Section(Single Phase Two Wire Mid-Point Earthed OS) calculation can be explained with given input values -> 1392.011 = (0.79*62^2*8.23*cos(0.5235987755982)^2)/(1.7E-05*890^2).

FAQ

What is Length of Wire using Area of X-Section(Single Phase Two Wire Mid-Point Earthed OS)?
The Length of Wire using Area of X-section(single Phase two Wire Mid-point Earthed OS) formula is defined as the total length of the wire that used in the single-phase two-wire mid-point earthed system and is represented as L = (A*Vm^2*Ploss*cos(Φ)^2)/(ρ*P^2) or Length of Overhead AC Wire = (Area of Overhead AC Wire*Maximum Voltage Overhead AC^2*Line Losses*cos(Phase Difference)^2)/(Resistivity*Power Transmitted^2). Area of Overhead AC Wire is defined as the cross-sectional area of the wire of an AC supply system, Maximum Voltage Overhead AC is defined as the peak amplitude of the AC voltage supplied to the line or wire, Line Losses is defined as the total losses occurring in an Overhead AC line when in use, Phase Difference is defined as the difference between the phasor of apparent and real power (in degrees) or between voltage and current in an ac circuit, Resistivity is the measure of how strongly a material opposes the flow of current through them & Power Transmitted is defined as the product of current and voltage phasor in a overhead ac line at the receiving end.
How to calculate Length of Wire using Area of X-Section(Single Phase Two Wire Mid-Point Earthed OS)?
The Length of Wire using Area of X-section(single Phase two Wire Mid-point Earthed OS) formula is defined as the total length of the wire that used in the single-phase two-wire mid-point earthed system is calculated using Length of Overhead AC Wire = (Area of Overhead AC Wire*Maximum Voltage Overhead AC^2*Line Losses*cos(Phase Difference)^2)/(Resistivity*Power Transmitted^2). To calculate Length of Wire using Area of X-Section(Single Phase Two Wire Mid-Point Earthed OS), you need Area of Overhead AC Wire (A), Maximum Voltage Overhead AC (Vm), Line Losses (Ploss), Phase Difference (Φ), Resistivity (ρ) & Power Transmitted (P). With our tool, you need to enter the respective value for Area of Overhead AC Wire, Maximum Voltage Overhead AC, Line Losses, Phase Difference, Resistivity & Power Transmitted and hit the calculate button. You can also select the units (if any) for Input(s) and the Output as well.
How many ways are there to calculate Length of Overhead AC Wire?
In this formula, Length of Overhead AC Wire uses Area of Overhead AC Wire, Maximum Voltage Overhead AC, Line Losses, Phase Difference, Resistivity & Power Transmitted. We can use 1 other way(s) to calculate the same, which is/are as follows -
  • Length of Overhead AC Wire = (Line Losses*Area of Overhead AC Wire)/(2*(Current Overhead AC)^2*Resistivity)