Line Losses Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS) Solution

STEP 0: Pre-Calculation Summary
Formula Used
line_losses = (Length*Resistivity*(Power Transmitted^2))/(Area Of 1-Φ 2-wire mid-point system*(Maximum Voltage^2)*((cos(Theta))^2))
W = (l*ρ*(P^2))/(a5*(Vm^2)*((cos(ϑ))^2))
This formula uses 1 Functions, 6 Variables
Functions Used
cos - Trigonometric cosine function, cos(Angle)
Variables Used
Length - Length is the measurement or extent of something from end to end. (Measured in Meter)
Resistivity - Resistivity is the measure of how strongly a material opposes the flow of current through them. (Measured in Ohm Meter)
Power Transmitted - The Power Transmitted Value through a shaft. (Measured in Kilowatt)
Area Of 1-Φ 2-wire mid-point system - The Area Of 1-Φ 2-wire mid-point system is the amount of two-dimensional space taken up by an object. (Measured in Square Meter)
Maximum Voltage - Maximum Voltage the highest voltage rating for electrical devices (Measured in Volt)
Theta - Theta is an angle that can be defined as the figure formed by two rays meeting at a common endpoint. (Measured in Degree)
STEP 1: Convert Input(s) to Base Unit
Length: 3 Meter --> 3 Meter No Conversion Required
Resistivity: 1.7E-05 Ohm Meter --> 1.7E-05 Ohm Meter No Conversion Required
Power Transmitted: 10 Kilowatt --> 10000 Watt (Check conversion here)
Area Of 1-Φ 2-wire mid-point system: 6 Square Meter --> 6 Square Meter No Conversion Required
Maximum Voltage: 60 Volt --> 60 Volt No Conversion Required
Theta: 30 Degree --> 0.5235987755982 Radian (Check conversion here)
STEP 2: Evaluate Formula
Substituting Input Values in Formula
W = (l*ρ*(P^2))/(a5*(Vm^2)*((cos(ϑ))^2)) --> (3*1.7E-05*(10000^2))/(6*(60^2)*((cos(0.5235987755982))^2))
Evaluating ... ...
W = 0.314814814814815
STEP 3: Convert Result to Output's Unit
0.314814814814815 Watt --> No Conversion Required
FINAL ANSWER
0.314814814814815 Watt <-- Line Losses
(Calculation completed in 00.032 seconds)

9 Area Of X-Section Calculators

Power Transmitted Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS)
power_transmitted = sqrt((Area Of 1-Φ 2-wire mid-point system*(Maximum Voltage^2)*Line Losses*((cos(Theta))^2))/(Resistivity*Length)) Go
Maximum Voltage Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS)
maximum_voltage = sqrt((Length*Resistivity*(Power Transmitted^2))/(Area Of 1-Φ 2-wire mid-point system*Line Losses*((cos(Theta))^2))) Go
RMS Voltage Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS)
rms_voltage = sqrt((2*Length*Resistivity*(Power Transmitted^2))/(Area Of 1-Φ 2-wire mid-point system*Line Losses*((cos(Theta))^2))) Go
Power Factor Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS)
power_factor = sqrt((Power Transmitted^2)*Resistivity*Length/(Area Of 1-Φ 2-wire mid-point system*Line Losses*(Maximum Voltage^2))) Go
Line Losses Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS)
line_losses = (Length*Resistivity*(Power Transmitted^2))/(Area Of 1-Φ 2-wire mid-point system*(Maximum Voltage^2)*((cos(Theta))^2)) Go
Length Of Wire Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS)
length = Area Of 1-Φ 2-wire mid-point system*(Maximum Voltage^2)*Line Losses*((cos(Theta))^2)/(Resistivity*(Power Transmitted^2)) Go
Resistivity Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS)
resistivity = Area Of 1-Φ 2-wire mid-point system*(Maximum Voltage^2)*Line Losses*((cos(Theta))^2)/(Length*(Power Transmitted^2)) Go
Load Current Using Area Of X-Section(1-Phase 2-Wire Mid-point Earthed OS)
current5 = sqrt(Area Of 1-Φ 2-wire mid-point system*Line Losses/(2*Resistivity*Length)) Go
Volume Of Conductor Material Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS)
volume_of_conductor_material = (2)*Area Of 1-Φ 2-wire mid-point system*Length Go

Line Losses Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS) Formula

line_losses = (Length*Resistivity*(Power Transmitted^2))/(Area Of 1-Φ 2-wire mid-point system*(Maximum Voltage^2)*((cos(Theta))^2))
W = (l*ρ*(P^2))/(a5*(Vm^2)*((cos(ϑ))^2))

What is the value of maximum voltage and volume of conductor material in this system?

The volume of conductor material required in this system is 1/2cos2θ times that of 2-wire d.c.system with the one conductor earthed. The maximum voltage between conductors is 2vm so that r.m.s. value of voltage between them is √2vm.

How to Calculate Line Losses Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS)?

Line Losses Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS) calculator uses line_losses = (Length*Resistivity*(Power Transmitted^2))/(Area Of 1-Φ 2-wire mid-point system*(Maximum Voltage^2)*((cos(Theta))^2)) to calculate the Line Losses, The Line Losses Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS) formula is defined as the loss of electric energy due to the heating of line wires by the current. Line Losses and is denoted by W symbol.

How to calculate Line Losses Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS) using this online calculator? To use this online calculator for Line Losses Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS), enter Length (l), Resistivity (ρ), Power Transmitted (P), Area Of 1-Φ 2-wire mid-point system (a5), Maximum Voltage (Vm) and Theta (ϑ) and hit the calculate button. Here is how the Line Losses Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS) calculation can be explained with given input values -> 0.314815 = (3*1.7E-05*(10000^2))/(6*(60^2)*((cos(0.5235987755982))^2)).

FAQ

What is Line Losses Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS)?
The Line Losses Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS) formula is defined as the loss of electric energy due to the heating of line wires by the current and is represented as W = (l*ρ*(P^2))/(a5*(Vm^2)*((cos(ϑ))^2)) or line_losses = (Length*Resistivity*(Power Transmitted^2))/(Area Of 1-Φ 2-wire mid-point system*(Maximum Voltage^2)*((cos(Theta))^2)). Length is the measurement or extent of something from end to end, Resistivity is the measure of how strongly a material opposes the flow of current through them, The Power Transmitted Value through a shaft, The Area Of 1-Φ 2-wire mid-point system is the amount of two-dimensional space taken up by an object, Maximum Voltage the highest voltage rating for electrical devices and Theta is an angle that can be defined as the figure formed by two rays meeting at a common endpoint.
How to calculate Line Losses Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS)?
The Line Losses Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS) formula is defined as the loss of electric energy due to the heating of line wires by the current is calculated using line_losses = (Length*Resistivity*(Power Transmitted^2))/(Area Of 1-Φ 2-wire mid-point system*(Maximum Voltage^2)*((cos(Theta))^2)). To calculate Line Losses Using Area Of X-section(1-Phase 2-Wire Mid-point Earthed OS), you need Length (l), Resistivity (ρ), Power Transmitted (P), Area Of 1-Φ 2-wire mid-point system (a5), Maximum Voltage (Vm) and Theta (ϑ). With our tool, you need to enter the respective value for Length, Resistivity, Power Transmitted, Area Of 1-Φ 2-wire mid-point system, Maximum Voltage and Theta and hit the calculate button. You can also select the units (if any) for Input(s) and the Output as well.
How many ways are there to calculate Line Losses?
In this formula, Line Losses uses Length, Resistivity, Power Transmitted, Area Of 1-Φ 2-wire mid-point system, Maximum Voltage and Theta. We can use 9 other way(s) to calculate the same, which is/are as follows -
  • length = Area Of 1-Φ 2-wire mid-point system*(Maximum Voltage^2)*Line Losses*((cos(Theta))^2)/(Resistivity*(Power Transmitted^2))
  • resistivity = Area Of 1-Φ 2-wire mid-point system*(Maximum Voltage^2)*Line Losses*((cos(Theta))^2)/(Length*(Power Transmitted^2))
  • power_transmitted = sqrt((Area Of 1-Φ 2-wire mid-point system*(Maximum Voltage^2)*Line Losses*((cos(Theta))^2))/(Resistivity*Length))
  • line_losses = (Length*Resistivity*(Power Transmitted^2))/(Area Of 1-Φ 2-wire mid-point system*(Maximum Voltage^2)*((cos(Theta))^2))
  • maximum_voltage = sqrt((Length*Resistivity*(Power Transmitted^2))/(Area Of 1-Φ 2-wire mid-point system*Line Losses*((cos(Theta))^2)))
  • rms_voltage = sqrt((2*Length*Resistivity*(Power Transmitted^2))/(Area Of 1-Φ 2-wire mid-point system*Line Losses*((cos(Theta))^2)))
  • power_factor = sqrt((Power Transmitted^2)*Resistivity*Length/(Area Of 1-Φ 2-wire mid-point system*Line Losses*(Maximum Voltage^2)))
  • current5 = sqrt(Area Of 1-Φ 2-wire mid-point system*Line Losses/(2*Resistivity*Length))
  • volume_of_conductor_material = (2)*Area Of 1-Φ 2-wire mid-point system*Length