Pressure Loss at Suction Solution

STEP 0: Pre-Calculation Summary
Formula Used
Dynamic Pressure Loss = Dynamic Loss Coefficient*0.6*Velocity of Air^2
Pd = C*0.6*V^2
This formula uses 3 Variables
Variables Used
Dynamic Pressure Loss - (Measured in Pascal) - Dynamic Pressure Loss is defined as the loss of pressure is due to the loss of the energy of the fluid in overcoming such dynamic forces resisting the changes.
Dynamic Loss Coefficient - Dynamic Loss Coefficient is defined as the value which is experimentally determined to calculate the dynamic pressure loss.
Velocity of Air - (Measured in Meter per Second) - The Velocity of Air is defined as the rate of air movement measured in distance traveled relative to the time elapsed.
STEP 1: Convert Input(s) to Base Unit
Dynamic Loss Coefficient: 0.02 --> No Conversion Required
Velocity of Air: 35 Meter per Second --> 35 Meter per Second No Conversion Required
STEP 2: Evaluate Formula
Substituting Input Values in Formula
Pd = C*0.6*V^2 --> 0.02*0.6*35^2
Evaluating ... ...
Pd = 14.7
STEP 3: Convert Result to Output's Unit
14.7 Pascal -->1.49847094801223 Millimeter Water (4 °C) (Check conversion here)
FINAL ANSWER
1.49847094801223 1.498471 Millimeter Water (4 °C) <-- Dynamic Pressure Loss
(Calculation completed in 00.004 seconds)

Credits

Vishwakarma Institute of Information Technology, Pune (VIIT Pune), Pune
Abhishek Dharmendra Bansile has created this Calculator and 100+ more calculators!
Verified by Anshika Arya
National Institute Of Technology (NIT), Hamirpur
Anshika Arya has verified this Calculator and 2500+ more calculators!

12 Dynamic loss in ducts Calculators

Pressure Loss due to Gradual Contraction given Pressure Loss Coefficient at Section 1
Go Dynamic Pressure Loss = 0.6*Velocity of Air at Section 1^2*Pressure Loss Coefficient*Pressure Loss Coefficient at 1
Pressure Loss due to Gradual Contraction given Velocity of Air at Point 2
Go Dynamic Pressure Loss = 0.6*Velocity of Air at Section 2^2*Pressure Loss Coefficient*Pressure Loss Coefficient at 2
Dynamic Loss Coefficient given Equivalent Additional Length
Go Dynamic Loss Coefficient = (Friction Factor in Duct*Equivalent Additional Length)/Hydraulic Mean Depth
Pressure Loss Coefficient at Outlet of Duct
Go Pressure Loss Coefficient at 2 = (Cross-Sectional Area of Duct at Section 2/Cross-Sectional Area of Duct at Section 1-1)^2
Pressure Loss Coefficient at Inlet of Duct
Go Pressure Loss Coefficient at 1 = (1-Cross-Sectional Area of Duct at Section 1/Cross-Sectional Area of Duct at Section 2)^2
Pressure Loss due to Sudden Contraction given Velocity of Air at point 2
Go Dynamic Pressure Loss = 0.6*Velocity of Air at Section 2^2*Pressure Loss Coefficient at 2
Pressure Loss due to Sudden Enlargement
Go Dynamic Pressure Loss = 0.6*(Velocity of Air at Section 1-Velocity of Air at Section 2)^2
Pressure Loss due to Sudden Contraction given Velocity of Air at Point 1
Go Dynamic Pressure Loss = 0.6*Velocity of Air at Section 1^2*Dynamic Loss Coefficient
Dynamic Loss Coefficient given Dynamic Pressure Loss
Go Dynamic Loss Coefficient = Dynamic Pressure Loss/(0.6*Velocity of Air^2)
Pressure Loss at Suction
Go Dynamic Pressure Loss = Dynamic Loss Coefficient*0.6*Velocity of Air^2
Dynamic Pressure Loss
Go Dynamic Pressure Loss = Dynamic Loss Coefficient*0.6*Velocity of Air^2
Pressure Loss at Discharge or Exit
Go Dynamic Pressure Loss = 0.6*Velocity of Air^2

Pressure Loss at Suction Formula

Dynamic Pressure Loss = Dynamic Loss Coefficient*0.6*Velocity of Air^2
Pd = C*0.6*V^2

Pressure loss at Suction.

In case of an abrupt suction opening, the air is accelerated as it
approaches the opening, forming a vena contracta inside the duct. The area changes from infinity to the duct area. In such a case, the loss coefficient C is taken as 0.85. By making a flanged entrance, the loss coefficient is reduced to 0.34. The loss coefficient can be further reduced to 0.03 by making the formed entrance of bell-mouth shape

How to Calculate Pressure Loss at Suction?

Pressure Loss at Suction calculator uses Dynamic Pressure Loss = Dynamic Loss Coefficient*0.6*Velocity of Air^2 to calculate the Dynamic Pressure Loss, The Pressure loss at suction formula is defined as the amount of pressure loss at the suction of ducts. Dynamic Pressure Loss is denoted by Pd symbol.

How to calculate Pressure Loss at Suction using this online calculator? To use this online calculator for Pressure Loss at Suction, enter Dynamic Loss Coefficient (C) & Velocity of Air (V) and hit the calculate button. Here is how the Pressure Loss at Suction calculation can be explained with given input values -> 0.152749 = 0.02*0.6*35^2.

FAQ

What is Pressure Loss at Suction?
The Pressure loss at suction formula is defined as the amount of pressure loss at the suction of ducts and is represented as Pd = C*0.6*V^2 or Dynamic Pressure Loss = Dynamic Loss Coefficient*0.6*Velocity of Air^2. Dynamic Loss Coefficient is defined as the value which is experimentally determined to calculate the dynamic pressure loss & The Velocity of Air is defined as the rate of air movement measured in distance traveled relative to the time elapsed.
How to calculate Pressure Loss at Suction?
The Pressure loss at suction formula is defined as the amount of pressure loss at the suction of ducts is calculated using Dynamic Pressure Loss = Dynamic Loss Coefficient*0.6*Velocity of Air^2. To calculate Pressure Loss at Suction, you need Dynamic Loss Coefficient (C) & Velocity of Air (V). With our tool, you need to enter the respective value for Dynamic Loss Coefficient & Velocity of Air and hit the calculate button. You can also select the units (if any) for Input(s) and the Output as well.
How many ways are there to calculate Dynamic Pressure Loss?
In this formula, Dynamic Pressure Loss uses Dynamic Loss Coefficient & Velocity of Air. We can use 7 other way(s) to calculate the same, which is/are as follows -
  • Dynamic Pressure Loss = Dynamic Loss Coefficient*0.6*Velocity of Air^2
  • Dynamic Pressure Loss = 0.6*(Velocity of Air at Section 1-Velocity of Air at Section 2)^2
  • Dynamic Pressure Loss = 0.6*Velocity of Air at Section 1^2*Dynamic Loss Coefficient
  • Dynamic Pressure Loss = 0.6*Velocity of Air at Section 2^2*Pressure Loss Coefficient at 2
  • Dynamic Pressure Loss = 0.6*Velocity of Air at Section 1^2*Pressure Loss Coefficient*Pressure Loss Coefficient at 1
  • Dynamic Pressure Loss = 0.6*Velocity of Air at Section 2^2*Pressure Loss Coefficient*Pressure Loss Coefficient at 2
  • Dynamic Pressure Loss = 0.6*Velocity of Air^2
Let Others Know
Facebook
Twitter
Reddit
LinkedIn
Email
WhatsApp
Copied!