Sending End Current using Impedance in End Condenser Method Solution

STEP 0: Pre-Calculation Summary
Formula Used
Sending End Current in ECM = (Sending End Voltage in ECM-Receiving End Voltage in ECM)/Impedance in ECM
Is(ecm) = (Vs(ecm)-Vr(ecm))/Zecm
This formula uses 4 Variables
Variables Used
Sending End Current in ECM - (Measured in Ampere) - Sending End Current in ECM is defined as the amount of current injected into a medium transmission line from the source or injectors.
Sending End Voltage in ECM - (Measured in Volt) - Sending End Voltage in ECM is the voltage at the sending end of a transmission line.
Receiving End Voltage in ECM - (Measured in Volt) - Receiving End Voltage in ECM is the voltage developed at the receiving end of a transmission line.
Impedance in ECM - (Measured in Ohm) - Impedance in ECM is defined as the amount of opposition faced by the direct or alternating current when it passes through a conductor component, circuit.
STEP 1: Convert Input(s) to Base Unit
Sending End Voltage in ECM: 400 Volt --> 400 Volt No Conversion Required
Receiving End Voltage in ECM: 256 Volt --> 256 Volt No Conversion Required
Impedance in ECM: 9 Ohm --> 9 Ohm No Conversion Required
STEP 2: Evaluate Formula
Substituting Input Values in Formula
Is(ecm) = (Vs(ecm)-Vr(ecm))/Zecm --> (400-256)/9
Evaluating ... ...
Is(ecm) = 16
STEP 3: Convert Result to Output's Unit
16 Ampere --> No Conversion Required
FINAL ANSWER
16 Ampere <-- Sending End Current in ECM
(Calculation completed in 00.020 seconds)

Credits

Created by Urvi Rathod
Vishwakarma Government Engineering College (VGEC), Ahmedabad
Urvi Rathod has created this Calculator and 1500+ more calculators!
Verified by Kethavath Srinath
Osmania University (OU), Hyderabad
Kethavath Srinath has verified this Calculator and 1200+ more calculators!

17 End Condenser Method in Medium Line Calculators

Receiving End Angle using Sending End Power in End Condenser Method
Go Receiving End Phase Angle in ECM = acos((Sending End Power in ECM-Power Loss in ECM)/(3*Receiving End Current in ECM*Receiving End Voltage in ECM))
Voltage Regulation in End Condenser Method
Go Voltage Regulation in ECM = (Sending End Voltage in ECM-Receiving End Voltage in ECM)/Receiving End Voltage in ECM
Sending End Current using Impedance in End Condenser Method
Go Sending End Current in ECM = (Sending End Voltage in ECM-Receiving End Voltage in ECM)/Impedance in ECM
Receiving End Voltage in End Condenser Method
Go Receiving End Voltage in ECM = Sending End Voltage in ECM-(Sending End Current in ECM*Impedance in ECM)
Sending End Voltage in End Condenser Method
Go Sending End Voltage in ECM = Receiving End Voltage in ECM+(Sending End Current in ECM*Impedance in ECM)
Impedance(ECM)
Go Impedance in ECM = (Sending End Voltage in ECM-Receiving End Voltage in ECM)/Sending End Current in ECM
Sending End Current using Losses in End Condenser Method
Go Sending End Current in ECM = sqrt(Power Loss in ECM/(3*Resistance in ECM))
Transmission Efficiency in End Condenser Method
Go Transmission Efficiency in ECM = (Receiving End Power in ECM/Sending End Power in ECM)*100
Receiving End Current in End Condenser Method
Go Receiving End Current in ECM = Sending End Current in ECM-Capacitive Current in ECM
Sending End Current in End Condenser Method
Go Sending End Current in ECM = Receiving End Current in ECM+Capacitive Current in ECM
Capacitive Current in End Condenser Method
Go Capacitive Current in ECM = Sending End Current in ECM-Receiving End Current in ECM
Sending End Power in End Condenser Method
Go Sending End Power in ECM = Receiving End Power in ECM-Power Loss in ECM
Resistance using Losses in End Condenser Method
Go Resistance in ECM = Power Loss in ECM/(3*Sending End Current in ECM^2)
Line Losses in End Condenser Method
Go Power Loss in ECM = 3*Resistance in ECM*Sending End Current in ECM^2
Admittance using A Parameter in End Condenser Method
Go Admittance in ECM = (2*(A Parameter in ECM-1))/Impedance in ECM
Impedance using A Parameter in End Condenser Method
Go Impedance in ECM = (2*(A Parameter in ECM-1))/Admittance in ECM
Medium Line A Parameter (LEC)
Go A Parameter in ECM = 1+((Impedance in ECM*Admittance in ECM)/2)

Sending End Current using Impedance in End Condenser Method Formula

Sending End Current in ECM = (Sending End Voltage in ECM-Receiving End Voltage in ECM)/Impedance in ECM
Is(ecm) = (Vs(ecm)-Vr(ecm))/Zecm

What are the disadvantages of condenser end?

Although the end condenser method for the solution of medium lines is simple to work out calculations, yet it has the following drawbacks. There is a considerable error (about 10%) in calculations because the distributed capacitance has been assumed to be lumped or concentrated.

What is end condenser method?

In this method, the capacitance of the line is lumped or concentrated at the receiving or load end. This method of localizing the line capacitance at the load end overestimates the effects of capacitance.

How to Calculate Sending End Current using Impedance in End Condenser Method?

Sending End Current using Impedance in End Condenser Method calculator uses Sending End Current in ECM = (Sending End Voltage in ECM-Receiving End Voltage in ECM)/Impedance in ECM to calculate the Sending End Current in ECM, The Sending End Current using Impedance in End Condenser Method formula is defined as the current at the sending end of the medium transmission lines. Sending End Current in ECM is denoted by Is(ecm) symbol.

How to calculate Sending End Current using Impedance in End Condenser Method using this online calculator? To use this online calculator for Sending End Current using Impedance in End Condenser Method, enter Sending End Voltage in ECM (Vs(ecm)), Receiving End Voltage in ECM (Vr(ecm)) & Impedance in ECM (Zecm) and hit the calculate button. Here is how the Sending End Current using Impedance in End Condenser Method calculation can be explained with given input values -> 8.888889 = (400-256)/9.

FAQ

What is Sending End Current using Impedance in End Condenser Method?
The Sending End Current using Impedance in End Condenser Method formula is defined as the current at the sending end of the medium transmission lines and is represented as Is(ecm) = (Vs(ecm)-Vr(ecm))/Zecm or Sending End Current in ECM = (Sending End Voltage in ECM-Receiving End Voltage in ECM)/Impedance in ECM. Sending End Voltage in ECM is the voltage at the sending end of a transmission line, Receiving End Voltage in ECM is the voltage developed at the receiving end of a transmission line & Impedance in ECM is defined as the amount of opposition faced by the direct or alternating current when it passes through a conductor component, circuit.
How to calculate Sending End Current using Impedance in End Condenser Method?
The Sending End Current using Impedance in End Condenser Method formula is defined as the current at the sending end of the medium transmission lines is calculated using Sending End Current in ECM = (Sending End Voltage in ECM-Receiving End Voltage in ECM)/Impedance in ECM. To calculate Sending End Current using Impedance in End Condenser Method, you need Sending End Voltage in ECM (Vs(ecm)), Receiving End Voltage in ECM (Vr(ecm)) & Impedance in ECM (Zecm). With our tool, you need to enter the respective value for Sending End Voltage in ECM, Receiving End Voltage in ECM & Impedance in ECM and hit the calculate button. You can also select the units (if any) for Input(s) and the Output as well.
How many ways are there to calculate Sending End Current in ECM?
In this formula, Sending End Current in ECM uses Sending End Voltage in ECM, Receiving End Voltage in ECM & Impedance in ECM. We can use 2 other way(s) to calculate the same, which is/are as follows -
  • Sending End Current in ECM = Receiving End Current in ECM+Capacitive Current in ECM
  • Sending End Current in ECM = sqrt(Power Loss in ECM/(3*Resistance in ECM))
Let Others Know
Facebook
Twitter
Reddit
LinkedIn
Email
WhatsApp
Copied!