Zero Sequence Voltage using A-Phase Current (LGF) Solution

STEP 0: Pre-Calculation Summary
Formula Used
Zero Sequence Voltage LG = (Fault Impedance LG*A-Phase Current LG)-(Negative Sequence Voltage LG)-(Positive Sequence Voltage LG)
V0(lg) = (Zf(lg)*Ia(lg))-(V2(lg))-(V1(lg))
This formula uses 5 Variables
Variables Used
Zero Sequence Voltage LG - (Measured in Volt) - Zero Sequence Voltage LG consists of a balanced three-phase voltage and current, phasors of which all have the same phase angles and rotate counterclockwise together.
Fault Impedance LG - (Measured in Ohm) - Fault Impedance LG is a measure of the resistance and reactance in an electrical circuit that is used to calculate the fault current that flows through the circuit in the event of a fault.
A-Phase Current LG - (Measured in Ampere) - A-phase Current LG is the current that flows into the a-phase in open conductor fault.
Negative Sequence Voltage LG - (Measured in Volt) - Negative Sequence Voltage LG consists of balanced three-phase voltage and current phasors which are exactly at 120 degrees apart rotating counterclockwise in ACB rotation.
Positive Sequence Voltage LG - (Measured in Volt) - Positive Sequence Voltage LG consists of balanced three-phase voltage and current phasors which are exactly at 120 degrees apart rotating counterclockwise in ABC rotation.
STEP 1: Convert Input(s) to Base Unit
Fault Impedance LG: 1.5 Ohm --> 1.5 Ohm No Conversion Required
A-Phase Current LG: 2.13 Ampere --> 2.13 Ampere No Conversion Required
Negative Sequence Voltage LG: 16.056 Volt --> 16.056 Volt No Conversion Required
Positive Sequence Voltage LG: 17.5 Volt --> 17.5 Volt No Conversion Required
STEP 2: Evaluate Formula
Substituting Input Values in Formula
V0(lg) = (Zf(lg)*Ia(lg))-(V2(lg))-(V1(lg)) --> (1.5*2.13)-(16.056)-(17.5)
Evaluating ... ...
V0(lg) = -30.361
STEP 3: Convert Result to Output's Unit
-30.361 Volt --> No Conversion Required
FINAL ANSWER
-30.361 Volt <-- Zero Sequence Voltage LG
(Calculation completed in 00.004 seconds)

Credits

Created by Urvi Rathod
Vishwakarma Government Engineering College (VGEC), Ahmedabad
Urvi Rathod has created this Calculator and 1500+ more calculators!
Verified by Payal Priya
Birsa Institute of Technology (BIT), Sindri
Payal Priya has verified this Calculator and 1900+ more calculators!

16 Voltage & EMF Calculators

Positive Sequence Voltage using A-Phase EMF and Sequence Impedances(LGF)
Go Positive Sequence Voltage LG = (A Phase EMF LG*(Zero Sequence Impedance LG+Negative Sequence Impedance LG))/(Zero Sequence Impedance LG+Positive Sequence Impedance LG+Negative Sequence Impedance LG)
Negative Sequence Voltage using A-Phase EMF and Sequence Impedances(LGF)
Go Negative Sequence Voltage LG = (-A Phase EMF LG*Negative Sequence Impedance LG)/(Zero Sequence Impedance LG+Positive Sequence Impedance LG+Negative Sequence Impedance LG)
A-Phase EMF using Negative Sequence Current (LGF)
Go A Phase EMF LG = Negative Sequence Current LG*((3*Fault Impedance LG)+Zero Sequence Impedance LG+Positive Sequence Impedance LG+Negative Sequence Impedance LG)
A-Phase EMF using Positive Sequence Current(LGF)
Go A Phase EMF LG = Positive Sequence Current LG*((3*Fault Impedance LG)+Zero Sequence Impedance LG+Positive Sequence Impedance LG+Negative Sequence Impedance LG)
A-Phase EMF using Zero Sequence Current (LGF)
Go A Phase EMF LG = Zero Sequence Current LG*((3*Fault Impedance LG)+Zero Sequence Impedance LG+Positive Sequence Impedance LG+Negative Sequence Impedance LG)
Zero Sequence Voltage using Positive Sequence Current
Go Zero Sequence Voltage LG = (3*Fault Impedance LG*Positive Sequence Current LG)-Negative Sequence Voltage LG-Positive Sequence Voltage LG
Zero Sequence Voltage using A-Phase Current (LGF)
Go Zero Sequence Voltage LG = (Fault Impedance LG*A-Phase Current LG)-(Negative Sequence Voltage LG)-(Positive Sequence Voltage LG)
Negative Sequence Voltage using A-Phase Current (LGF)
Go Negative Sequence Voltage LG = (Fault Impedance LG*A-Phase Current LG)-Positive Sequence Voltage LG-Zero Sequence Voltage LG
Zero Sequence Voltage using Phase Voltages(LGF)
Go Zero Sequence Voltage LG = 1/3*(Fault Impedance LG*A-Phase Current LG+B Phase Voltage LG+C Phase Voltage LG)
Positive Sequence Voltage for L-G-F
Go Positive Sequence Voltage LG = EMF Induced in Primary Winding LG-(Positive Sequence Impedance LG*Positive Sequence Current LG)
A-Phase EMF using Positive Sequence Voltage (LGF)
Go A Phase EMF LG = Positive Sequence Voltage LG+(Positive Sequence Impedance LG*Positive Sequence Current LG)
A-Phase Voltage using Sequence Voltages(LGF)
Go A Phase Voltage LG = Zero Sequence Voltage LG+Positive Sequence Voltage LG+Negative Sequence Voltage LG
Negative Sequence Voltage for LGF
Go Negative Sequence Voltage LG = -Negative Sequence Impedance LG*Negative Sequence Current LG
Positive Sequence Voltage using Positive Sequence Current
Go Positive Sequence Voltage LG = 3*Fault Impedance LG*Positive Sequence Current LG
Zero Sequence Voltage for LGF
Go Zero Sequence Voltage LG = -Zero Sequence Impedance LG*Zero Sequence Current LG
A-Phase Voltage(LGF)
Go A Phase Voltage LG = Fault Impedance LG*A-Phase Current LG

Zero Sequence Voltage using A-Phase Current (LGF) Formula

Zero Sequence Voltage LG = (Fault Impedance LG*A-Phase Current LG)-(Negative Sequence Voltage LG)-(Positive Sequence Voltage LG)
V0(lg) = (Zf(lg)*Ia(lg))-(V2(lg))-(V1(lg))

What are the Sequence Components?

The positive sequence consists of balanced three-phase voltage and current phasors which are exactly at 120 degrees apart rotating counterclockwise in ABC rotation. The negative sequence consists of balanced three-phase voltage and current phasors which are exactly at 120 degrees apart rotating counterclockwise in ACB rotation. Zero sequence consists of a balanced three-phase voltage and current, phasors of which all have the same phase angles and rotate counterclockwise together.

How to Calculate Zero Sequence Voltage using A-Phase Current (LGF)?

Zero Sequence Voltage using A-Phase Current (LGF) calculator uses Zero Sequence Voltage LG = (Fault Impedance LG*A-Phase Current LG)-(Negative Sequence Voltage LG)-(Positive Sequence Voltage LG) to calculate the Zero Sequence Voltage LG, The Zero Sequence Voltage using a-phase current (LGF) formula is defined as consists of a balanced three-phase voltage and current, phasors of which all have the same phase angles and rotate counterclockwise together. Zero Sequence Voltage LG is denoted by V0(lg) symbol.

How to calculate Zero Sequence Voltage using A-Phase Current (LGF) using this online calculator? To use this online calculator for Zero Sequence Voltage using A-Phase Current (LGF), enter Fault Impedance LG (Zf(lg)), A-Phase Current LG (Ia(lg)), Negative Sequence Voltage LG (V2(lg)) & Positive Sequence Voltage LG (V1(lg)) and hit the calculate button. Here is how the Zero Sequence Voltage using A-Phase Current (LGF) calculation can be explained with given input values -> -30.361 = (1.5*2.13)-(16.056)-(17.5).

FAQ

What is Zero Sequence Voltage using A-Phase Current (LGF)?
The Zero Sequence Voltage using a-phase current (LGF) formula is defined as consists of a balanced three-phase voltage and current, phasors of which all have the same phase angles and rotate counterclockwise together and is represented as V0(lg) = (Zf(lg)*Ia(lg))-(V2(lg))-(V1(lg)) or Zero Sequence Voltage LG = (Fault Impedance LG*A-Phase Current LG)-(Negative Sequence Voltage LG)-(Positive Sequence Voltage LG). Fault Impedance LG is a measure of the resistance and reactance in an electrical circuit that is used to calculate the fault current that flows through the circuit in the event of a fault, A-phase Current LG is the current that flows into the a-phase in open conductor fault, Negative Sequence Voltage LG consists of balanced three-phase voltage and current phasors which are exactly at 120 degrees apart rotating counterclockwise in ACB rotation & Positive Sequence Voltage LG consists of balanced three-phase voltage and current phasors which are exactly at 120 degrees apart rotating counterclockwise in ABC rotation.
How to calculate Zero Sequence Voltage using A-Phase Current (LGF)?
The Zero Sequence Voltage using a-phase current (LGF) formula is defined as consists of a balanced three-phase voltage and current, phasors of which all have the same phase angles and rotate counterclockwise together is calculated using Zero Sequence Voltage LG = (Fault Impedance LG*A-Phase Current LG)-(Negative Sequence Voltage LG)-(Positive Sequence Voltage LG). To calculate Zero Sequence Voltage using A-Phase Current (LGF), you need Fault Impedance LG (Zf(lg)), A-Phase Current LG (Ia(lg)), Negative Sequence Voltage LG (V2(lg)) & Positive Sequence Voltage LG (V1(lg)). With our tool, you need to enter the respective value for Fault Impedance LG, A-Phase Current LG, Negative Sequence Voltage LG & Positive Sequence Voltage LG and hit the calculate button. You can also select the units (if any) for Input(s) and the Output as well.
How many ways are there to calculate Zero Sequence Voltage LG?
In this formula, Zero Sequence Voltage LG uses Fault Impedance LG, A-Phase Current LG, Negative Sequence Voltage LG & Positive Sequence Voltage LG. We can use 3 other way(s) to calculate the same, which is/are as follows -
  • Zero Sequence Voltage LG = -Zero Sequence Impedance LG*Zero Sequence Current LG
  • Zero Sequence Voltage LG = 1/3*(Fault Impedance LG*A-Phase Current LG+B Phase Voltage LG+C Phase Voltage LG)
  • Zero Sequence Voltage LG = (3*Fault Impedance LG*Positive Sequence Current LG)-Negative Sequence Voltage LG-Positive Sequence Voltage LG
Let Others Know
Facebook
Twitter
Reddit
LinkedIn
Email
WhatsApp
Copied!